By the means of the measurement values of voltage and current BLR-CX  calculates the conditions in the network. As standard the voltage L2-L3 and the current in L1 is used. By the means of a switchover in the device menu also single phase measurement can be adjusted (e.g. voltage L1-N / current in L1) if necessary. The sensitivity of the BLR-CX  is 10mA, whereby a reliable and accurate regulation is guaranteed. Either 1A or 5A current transformers can be used. The power factor regulator detects this autonomously and it adapts to the used type automatically. By the means of providing an independent auxiliary voltage, and measurement voltage, a voltage measurement range between 50 - 530V is possible in these relays.
 
 


By the use of the optional fan control the power factor relay, BLR-CX “L” can also measure out the ambient temperature inside the compensation system. If the temperature exceeds an adjustable threshold the integrated fan control relay directly switches on any connected fan to cool down the temperature inside the switchboard.
   
On the rear side, the power factor regulator BLR-CX is equipped with a TTL interface as standard. This interface can also be used for diagnostic purposes. By the use of a separate available adapter cable, this interface is transformed to an RS232 connection that can directly be connected to a PC. The software “WINBSTO” enables the user to make very easy and effective diagnostics. By this way problems can be detected very fast and afterwards they can be eliminated.


BLR CX / CXD range highlights
  
Fully-automatic c/k-value setting, self adapting, connection of different capacitor step sizes possible
Automatic detection and usage of the optimum capacitor step
Switching programs: automatic, LIFO, manual mode, combi -filter (on request)
Capable for 4-quadrant operation
1-phase measurement system also suitable for non sinusoidal currents and voltages
Supply voltage 415/115V, 45-65Hz, other voltages on request
Voltage measuring 50 – 530V, 45 – 65Hz
Current measuring 10mA – 5A, suitable for CT x/1A and x/5A
Connection with cage clamps
Commissioning can be performed, without any additional settings or programming
LED display for cos-phi and parameters
States of capacitor steps indicated via LED
Alarm relay with volt-free c/o contact. “AL” indication for defective steps, low PF, excess temperature
    TTL-interface on back