By means of the measurement values of
voltage and current BLR - CM calculates the
conditions in the network. As standard, the
voltage L1-N and current in L1 is used. The
separation of auxiliary voltage and voltage
measuring allows a voltage measuring range
between 50-530V. Additionally, there is the
possibility to change the phase-shift
between voltage and current in steps of 15
degrees. The result is the maximum possible
flexibility of the relay for applications
with voltage measuring phase/neutral,
phase/phase and for mixed measuring with
different transformer types.
The BLR-CM is measuring the temperature in
the panel by using the integrated
temperature sensor. This measurement value
can be handled flexible, eg; it can be used
for an alarm message. By the means of the
digital output an additional fan can be
activated
BLR CM highlights
Full-automatic c/k-value setting, self
adapting, connection of different capacitor
step sizes possible
Automatic detection and usage of the optimum
capacitor step
Manual mode possible
Multiple connection types possible through
adjustable phase compensation angle
Capable for 4-quadrant operation
Individually configurable discharging time
allows quicker switching time
1-phase measurement system also suitable for
non-sinusoidal currents and voltages
Graphical LCD for display of step status,
measurement values and system data
Measurement display for U, I, P, Q, S, THD
U, THD I, Q, F, T
Harmonics measurement for voltage and
current up to the 31. order
Counter for active and reactive work
Flexible alarm system with up to 15 alarms
Programmable digital input and digital
output
Programmable alarm relay with volt -free c/o
contact
Supply voltage 115/230V, 45-65Hz, other
voltages on request